0388655 ADJ.LEVER & SHAFT ASSY. JOHNSON
25E77S, 25E78C, 25E79R, 35E77C, 35E78R, 35E79A, J25RCSA, J35ECSM
ADJ
Price: query
Rating:
You can buy parts:
As an associate, we earn commssions on qualifying purchases through the links below
$50.00
21-07-2020
1.0[0.45] Pounds
-: -
0388655 Adjustment Lever & Shaft Evinrude 25 35HP Johnson OMC 388655
OMC || 0388655 || Used & Guaranteed Good Condition! || 1977-80 || 25, 35
OMC || 0388655 || Used & Guaranteed Good Condition! || 1977-80 || 25, 35
BRP JOHNSON entire parts catalog list:
- EXHAUST HOUSING-25 HP » 0388655
- EXHAUST HOUSING-35 HP
25E79R, 25EL79R, 25R79R, 25RL79R 1979
35E77C, 35E77H, 35EL77C, 35EL77H, 35R77C, 35R77H, 35RL77C, 35RL77H 1977
35E78R, 35EL78R, 35R78R, 35RL78R 1978
35E79A, 35EL79A, 35R79A, 35RL79A 1979
J25RCSA, J25RLCSA, J25TECSA, J25TELCSA 1980
J35ECSM, J35ELCSM, J35RCSM, J35RLCSM 1980
Information:
Illustration 1 g00679810
Simplified Schematic For The Engine Coolant Temperature SensorNote: This schematic is not for engines with an ECM. The ECM monitors the coolant temperature. The ECM sends the information to the GSC+. The following procedure DOES APPLY to engines with an ECM.In order to find the cause of a high water temperature shutdown, perform the following procedure.Test Step 1. CHECK FOR THE DIAGNOSTIC CODE.
Check for the following active diagnostic codes: CID 110 (coolant temperature sensor) and CID 269 (sensor power supply). See Testing And Adjusting, "Troubleshooting Diagnostic Codes".Expected Result:CID 110 or CID 269 should not be showing. This means that CID 110 or CID 269 are not active.Results:
OK - CID 110 or CID 269 are not showing. Proceed to Test Step 2.
NOT OK - CID 110 or CID 269 is active.Repair: Correct the active CID 110 or CID 269 prior to proceeding with this procedure. See the topic Testing And Adjusting, "Troubleshooting Diagnostic Codes". On engines with an ECM, see Troubleshooting, RENR5979, "G3500C Engines", "P-503", for EIS engines, seeTroubleshooting, SENR6535, "G3408C and G3412C Engines", "P-503". Stop.Test Step 2. CHECK OBVIOUS CAUSES.
Check the water level.
Check the fan drive belts.
Check for other obvious causes of high water temperature.Expected Result:No obvious cause should exist.Results:
OK - No obvious causes were found. Proceed to Test Step 3.
NOT OK - An obvious cause exists.Repair: Correct the problem. Refer to the Engine Service Manual. Stop.Test Step 3. CHECK SETPOINT P015.Note: Setpoint P015 describes high water temperature.
View setpoint P015. Make a note of setpoint P015. See System Operation, "Engine/Generator Setpoint Viewing OP2-0".
Compare the setpoints which are viewed with the specified setpoints of the particular generator set.Expected Result:The actual setpoint value and the specified setpoint value should agree.Results:
OK - The setpoints agree. Proceed to Test Step 4.
NOT OK - The setpoints do NOT agree.Repair: Reprogram setpoint P015. See System Operation, "Engine/Generator Programming OP5-0". Stop.Test Step 4. CHECK THE HIGH WATER TEMPERATURE FUNCTION.
Turn the engine control switch (ECS) to OFF/RESET. Then, turn the ECS to START.
Run the engine until the water temperature has stabilized.
Check and note the actual water temperature which is showing on the lower display.
Compare the actual temperature that is showing on the lower display with setpoint P015.Note: It may be necessary to check the accuracy of the temperature that is shown on the lower display of the GSC+. Install an accurate engine coolant temperature gauge. Install the sensor as close as possible to the EMCP II+ coolant temperature sensor.Expected Result:The actual temperature which is showing on the lower display should be less than setpoint P015. This actual temperature should not cause a high water temperature shutdown.Results:
Temp less than P015, indicator OFF - The actual temperature is less than the setpoint P015 and the high water temperature indicator does not FLASH. Repair: The problem is not present now. The problem may be intermittent. Check the harness. Check all of the electrical connections of the water temperature circuit. See Testing And Adjusting, "Electrical Connector - Inspect". Stop.
Temp less than P015, indicator FLASHING - The actual temperature is less than the setpoint P015 and the high water temperature indicator remains FLASHING.Repair: Therefore, the GSC+ has failed. Replace the GSC+. See Testing And Adjusting, "EMCP Electronic Control (Generator Set) - Replace". Stop.
Temp higher than P015 - Actual temperature is greater than the setpoint P015.Repair: The temperature is correct for a high water temperature shutdown. The engine should shutdown, and the indicator for high water temperature should FLASH. The GSC+ is operating properly. Refer to the Engine Service Manual in order to find the cause of high water temperature. Stop.