Probable Causes
The following probable causes apply if the generator is equipped with the EMCP II+:
There is an incorrect calibration value for the AC Transformer Box + (ATB+).
A potential transformer in the ATB+ is faulty.
A current transformer in the ATB+ is faulty.
The ATB+ is faulty.
There is an incorrect value for one or more of the parameters for the fuel.
There is an incorrect value for one or more of the "Power Monitoring" parameters.The following probable causes apply if the generator is equipped with a power sensor:
There is a faulty potential transformer for the power sensor.
There is a faulty current transformer for the power sensor.
The power sensor is faulty.
There is a problem with the wiring between the power sensor and the ECM.
There is an incorrect value for one or more of the parameters for the fuel.
The offset voltage from the power sensor is too high.
There is an incorrect value for one or more of the "Power Monitoring" parameters.Read the rest of this procedure before you adjust the "Power Monitoring" parameters.Recommended Repairs
Generators that are Equipped with EMCP II+
Verify that the transformers and the ATB+ are operating correctly. Refer to the appropriate service literature for the EMCP II+.Verify that the values for the "Air/Fuel Ratio Control" configuration parameters are correct. Refer to Systems Operation/Testing and Adjusting, "Electronic Control System Parameters".Verify that the values for the "Power Monitoring" configuration parameters are correct. Refer to Systems Operation/Testing and Adjusting, "Electronic Control System Parameters".Generators that are Equipped with a Power Sensor
Verify that the transformers for the power sensor are operating correctly. Refer to the service literature for the power sensor.Verify that the power sensor is operating correctly. Refer to the service literature for the power sensor.Verify that the values for the "Air/Fuel Ratio Control" configuration parameters are correct. Refer to Systems Operation/Testing and Adjusting, "Electronic Control System Parameters".Check the wiring between the power sensor and the ECM for corrosion and for pinch points. Refer to Troubleshooting, "Electrical Connectors - Inspect".The control system must receive an accurate voltage from the power sensor. When the generator's output is zero, the voltage from the power sensor must be less than 0.01 VDC. This voltage is called the offset voltage.Use the following procedure in order to determine if the offset voltage is too high. Perform this procedure before you adjust the "Power Monitoring" parameters.Note: The engine must be stopped. If the engine is equipped with an ASM, take the measurement at the P5 connector. If the engine is not equipped with an ASM, take the measurement at the P1 connector.
If the engine is running, stop the engine.
Insert 7X-1710 Multimeter Probes into terminals P1-19 and P1-25 or into P1-3 and P1-16. Connect a digital voltmeter to the probes. The polarity of the connections is not important.
Verify that the probes are making good contact with the terminals inside the connector. Measure the DC voltage at the terminals. The voltage is acceptable if the voltage is less than 0.01 VDC.If the voltage is less than 0.01 VDC, the values for the "Power Monitoring" parameters may be incorrect. Refer to Systems Operation/Testing and Adjusting, "Electronic Control System Parameters".If the voltage is greater than 0.01 VDC, the circuit between the power sensor and the ECM must be calibrated. Refer to Troubleshooting, "Generator Output Power Sensor - Set".


Parts housing JOHNSON:

5030634
HOUSING, Under oil seal
5030634 HOUSING, Under oil seal
BJ60PL4SDM, BJ60PL4SOA, BJ60PL4SRR, BJ60PL4STC, BJ70PL4SDM, BJ70PL4SOA, BJ70PL4SRR, BJ70PL4STC, J60PL4SNF, J70FLTLECS, J70PL4SNF
5032862
 
5032862 HOUSING, Propeller shaft brg
BJ60PL4SDM, BJ60PL4SOA, BJ60PL4SRR, BJ60PL4STC, BJ70PL4SDM, BJ70PL4SOA, BJ70PL4SRR, BJ70PL4STC, J60PL4SNF, J70PL4SNF
5032814
 
5032814 *HOUSING, TILLER HANDLE
BJ40PL4SDR, BJ40PL4SOC, BJ40PL4SRS, BJ50PL4SDR, BJ50PL4SOC, BJ50PL4SRS, BJ60PL4SDM, BJ60PL4SOA, BJ60PL4SRR, BJ60PL4STC, BJ70PL4SDM, BJ70PL4SOA, BJ70PL4SRR, BJ70PL4STC, J40PL4STC, J50PL4STC
5034633
 
5034633 HOUSING, Shift rod guide
BJ60PL4SDM, BJ60PL4SOA, BJ60PL4SRR, BJ70PL4SDM, BJ70PL4SOA, BJ70PL4SRR
Back to top