Information:


Table 1
J1939 Code and Description CDL Code and Description Comments
7417-2
Aftertreatment #1 DEF Controller : Erratic, Intermittent, or Incorrect E1607
Aftertreatment #1 DEF Control Module Circuit Breaker Open The 120 VAC circuit breaker has been turned off while the engine is running.
Table 2
Troubleshooting Test Steps Values Results
1. Check for Codes
A. Connect Cat® Electronic Technician (ET) to the service tool connector.
B. Determine if a code is active or logged.
Codes
Result: A code is active or logged.
Proceed to Test Step 2.
2. Check the AC Breaker In the Dosing Cabinet
A. Remove the cover to access the AC DEF pump circuit breaker.
B. Verify that the AC breaker is in the ON position.
Breaker
Result: The AC DEF pump circuit breaker is in the ON position.
Proceed to Test Step 4.
Result: The AC DEF pump circuit breaker is not in the ON position.
Proceed to Test Step 3.
3. Place the AC DEF Pump Circuit Breaker in the ON Position
Codes
Result: The AC DEF pump circuit breaker reset.
Proceed to Test Step 4.
Result:The AC DEF pump circuit breaker did not reset or immediately trips.
Repair:Troubleshoot AC DEF pump power supply circuit.
4. Operate the Engine
A. Remove electrical power from the engine for at least 1 minute.
B. Apply electrical power to the engine.
C. Start the engine.
D. Connect Cat ET.
E. Use Cat ET to monitor the following:
- Codes
Codes
Result: A code is not active.
Return to service.
Result: An 7417-2 code becomes active while running the engine and the breaker does not trip.
Proceed to Test Step 5.
5. Check the wiring to the AC DEF Pump Power Supply monitoring breaker that is mechanically linked to the AC DEF Pump power supply breaker.
A. Removes AC and DC power from the engine and aftertreatment systems.
B.Disconnect the J1 connector from the SCR controller in the dosing cabinet.
C. Place the AC DEF Pump Power Supply Breaker in the ON position.
D. Measure resistance between the following pins:
-J1-47
-J2-92
E. Place the AC DEF Pump Power Supply Breaker in the OFF position.
F. Measure resistance between the following pins:
-J1-46
-J2-92
Ohms Result: Both circuit checks indicated less than 10 ohms of resistance.
Proceed to Test Step 6.
Result: One or both circuit checks indicated more than 10 ohms of resistance.
Troubleshoot an open circuit on the wiring harness between the SCR controller and the AC DEF Pump Power Supply Monitoring Breaker.
6. Check wiring between the SCR controller and the AC DEF Pump Power Supply Monitoring Breaker for a short circuit to ground or pin to pin short.
A. Measure resistance between J1-47, J1-46, and J2-92 and a known good ground.
B. Measure resistance between J1-47, J1-46, and J2-92 and all other pins on the J1 connector.
Expect to have continuity between J1-47 and J2-92 when the breaker is in ON position.
Expect to have continuity between J1-46 and J2-92 when the breaker is in the OFF position.
Ohms
Result: The resistance value is less than 100K ohms on any of the three wires checked.
A short circuit to ground or wire to wire short in the wiring harness has been detected.
Repair: Repair or replace the wiring harness as necessary.
Result: The resistance value is more than 100K ohms between all three pins and a known good ground and all other pins on the J1 connector.
Repair: Replace the AC DEF Pump Power Supply Circuit breaker and proceed to Test Step 7.
7. Operate the Engine
A. Remove electrical power from the engine for at least one minute.
B. Apply electrical power to the engine.
C. Start the Engine.
D. Connect Cat ET.
E. Use Cat ET to monitor the following:
-7417-2
-E1607
Codes
Result: A code is not active.
Return to service.
Result: A code becomes active while running the engine. Contact your Technical Communicator for further assistance. If the procedure did not correct the issue, contact your Cat dealer Technical Communicator (TC). For further assistance, your TC can confer with the Dealer Solutions Network (DSN).


Parts bolt Mariner:

16705
 
16705 BOLT
7002201DK, 7002201HB, 7002201SK, 7002201UB, 7003201BK, 7004211SK, 7006201MK, 7006201UK, 7015203KL, 7025207UL, 7025217UL, 7030201KL, 7030201UL, 7030211U2, 7030A01UL, 7030A11UL, 7031207LF, 7040203KL, 7040203UL, 7A25203UK, 7A25213UL, 7A25302UL, 7A3G312U
16223 2
 
16223 2 BOLT
7040203KL, 7040203UL, 7F042016B, 7F04201JB
851866 4
 
851866 4 BOLT
7040203KL, 7040203UL, 7F08201TB, 7F15311ZK
823042 15
 
823042 15 BOLT
7040203KL
823042062
 
823042062 BOLT
7F08201TB
853531002
 
853531002 BOLT
7F08201TB
823042042
 
823042042 BOLT, Stainless Steel
7A25203UK, 7A25213UL, 7A25302UL, 7A3G312UK, 7F08201TB
879194192
Back to top