Information:


Illustration 1 g00487968
System Schematic For Generator Fault Relay (GFR)The GSC+ uses the generator fault relay (GFR) to activate the shunt trip coil of the optional circuit breaker during a shutdown fault. This circuit breaker takes the generator off the line during a shutdown fault. The GFR is located within the relay module. The optional circuit breaker is located in the generator housing and the shunt trip coil is located within the circuit breaker.Note: Whenever the GSC+ activates the GFR, "K2" is shown on the lower display. "K2" is also shown on the lower display when the GSC+ attempts to activate the GFR. When the GFR is not activated, "K2" is not shown.ProcedureThe possible cause of this diagnostic code is an open coil or a shorted coil of the GFR.The following response is the system response to this fault while the GFR is activated:
If a CID 442 occurs, then there is no effect on the system because the optional circuit breaker is already open. Also, the shutdown mode is functioning. The generator is already off the line.The following response is the system response to this fault while the GFR is not activated and a shutdown fault occurs:
If a CID 442 occurs, then the GFR cannot activate the shunt trip coil of the optional circuit breaker. The generator remains on-line.The GSC+ treats a CID 442 as an alarm fault. Active alarm faults are shown on the display when the alarm codes key is pressed. When the ECS is in any position except the OFF/RESETposition, the active alarm faults are shown. Clear the diagnostic code from the fault log after troubleshooting is complete.
Check the status of the diagnostic code (Active/Inactive).
Turn the ECS to OFF/RESET and then turn the ECS to STOP.
Press the alarm codes key.
Observe the upper display. Check that the diagnostic code is showing.
If the diagnostic code is not showing, enter the service mode. View the fault log (OP1). Check that the diagnostic code is showing. Expected Result: A CID 442 FMI 12 is showing as a active fault or an inactive fault. Results:
OK: A CID 442 FMI 12 has not occurred. The fault is NOT active and the fault is NOT inactive. STOP.
NOT OK: A CID 442 FMI 12 is active or inactive. Proceed to 2.
Check internal cable of relay module. Note: Only open the relay module in a dry environment. If the inspection takes more than twenty minutes replace the desiccant bag in the GSC+ housing. See Testing And Adjusting, "Relay Module - Replace".
Turn the ECS to OFF/RESET.
Temporarily, remove the relay module from the GSC+. See Testing And Adjusting, "Relay Module Replace".
Check the cable that attaches the relay module to the GSC+. Expected Result: The cable should be firmly seated in the connector. The clamp should be in place. The cable should not be damaged. Results:
OK: Reassemble the relay module to the GSC+. Proceed to 3.
NOT OK: If the connector clamp is missing, replace the connector clamp. If the cable is damaged, replace the GSC+. STOP.
Perform a functional check for the GFR.
Turn the ECS to OFF/RESET.
Disconnect all wires from RM-22 of the relay module.
At the relay module, measure the resistance from RM-22 to RM-7. Resistance should be greater than 5000 ohms.
Turn the ECS to STOP and push in the emergency stop button.
At the relay module, measure the resistance from RM-22 to RM-7. Resistance should be less than 5 ohms.Expected Result: For 3.c, the resistance should be greater than 5000 ohms. For 3.e, the resistance should be less than 5 ohms.Results:
OK: There was probably a poor connection.and this procedure corrected it. Check the electrical connectors, terminals and wiring. See Testing And Adjusting, "Electrical Connector - Inspect". STOP.
NOT OK: Either one of the resistance measurements are NOT correct. The relay module is faulty. Replace the relay module. See Testing And Adjusting, "Relay Module - Replace". STOP.


Parts bushing Mariner:

80043M
 
80043M BUSHING (UPPER)
7003207, 7005207, 7005227
82575M
 
82575M BUSHING
7005207, 7005227
82716M
 
82716M BUSHING
7005207, 7005227
81949M
 
81949M BUSHING
7004201, 7005201, 7005207, 7008208, 7008218EW, 7008238, 7008248, 7008305, 7008425, 7010209, 7015529, 7020201, 7025200, 7025207NW, 7025207PW, 7025208CW, 7025500, 7026226, 7028207, 7028527, 7030200, 7030205, 7030301, 7030320, 7040202, 7040206, 7040207,
91758M
 
91758M BUSHING
7004201, 7005201, 7005207
91760M
 
91760M BUSHING, RUBBER
7004201, 7005201, 7005207
96558M
 
96558M BUSHING
7004201, 7005201, 7005207
81936M
 
81936M BUSHING
7003207
Back to top