System Schematic For Starting Motor Relay (SMR)The starting motor remains engaged or the starting motor continues to run after the engine has started.
Check setpoints.This step checks setpoints P11 (crank terminate speed), P17 (total cycle crank time) and P18 (cycle crank time).
View and make a note of setpoints P11, P17 and P18. See Systems Operation, "Engine/Generator Setpoint Viewing OP2".
Compare the setpoints viewed with the specified setpoints of the particular generator set. The factory default value for P11 is 400 rpm. The factory default value for P17 is 90 seconds. The factory default value for P18 is 10 seconds.Note: Engines that are equipped with prelube pumps may require cycle crank times of 30 seconds or more.Expected Result: The viewed setpoint value and the specified setpoint value should agree.Results:
OK - Proceed to next step.
Not OK - The viewed setpoint does not agree with the specified setpoint. Reprogram setpoints P11, P17 and P18. See Systems Operation, "Engine/Generator Programming OP5". Proceed to next step.
Check the engine starting function.The remaining steps of this procedure require checks to be made during a simulated engine starting. The fuel delivery system is disabled.
Disable the engine ECM in order to prevent the engine from starting but not from cranking. Remove the "C key" on the J1 40-pin connector.
Prepare to manually stop the engine from cranking. If necessary, turn the battery disconnect switch to the OFF position or shut the engine off by mechanical means.
Turn the ECS to START and allow the engine to crank.
Turn the ECS to OFF/RESET.Expected Result: The engine should stop cranking.Results:
OK - Proceed to 6.
Not OK - Engine continues to crank. Proceed to next step.
Check the engine starting function (continued). The conditions of 2 remain. The fuel delivery is disabled and the engine is cranking.
While the engine is still cranking from the preceding step, push the emergency stop push button.Expected Result: The engine should stop cranking.Results:
OK - Check the wire on RM-18 of the relay module for a short to B+. If a short is not found, replace the relay module. See Testing And Adjusting, "Relay Module - Replace". STOP.
Not OK - Engine continues to crank. Proceed to next step.
Check the engine starting function (continued). The conditions of 3 remain. The fuel delivery is disabled and the engine is cranking.
Stop the engine. Turn the battery disconnect switch to the OFF position or shut the engine off by mechanical means.
Remove all wires from terminals TS1-25 in the generator housing. For dual starting motors, remove all the wires from terminal TS1-26.
Turn the ECS to the START position and attempt to crank the engine.Expected Result: The engine should not crank.Results:
OK - The engine does not crank. Therefore, the starting motor magnetic switch (SMMS) or related wiring is faulty. Troubleshoot the SMMS and the related wiring. See Testing And Adjusting, "Schematics & Wiring Diagram". STOP.
Not OK - Engine continues to crank. Proceed to next step.
Check the engine starting function (continued). The conditions of 4 remain. The fuel delivery is disabled and the engine is cranking.
Stop the engine. Turn the battery disconnect switch to the OFF position or shut the engine off by mechanical means.
Disconnect the B+ wire on the pinion solenoid of the starting motor.
Turn the ECS to START and attempt to crank the engine.Expected Result: The engine should not crank.Results:
OK - The engine does not crank. Therefore, the wire 304-WH-10 and/or the wire 314-PU-10 in the engine harness are shorted to the battery B+. Troubleshoot the wiring. See the "Generator Set Wiring Diagram" in Testing And Adjusting, "Schematics And Wiring Diagrams". STOP.
Not OK - Engine continues to crank. Therefore, the starting motor is faulty. Troubleshoot the starting motor. Refer to the Starting Motor Manual and/or the Engine Service Manuals.. STOP.
Check the starting motor cycling.This step continues troubleshooting from 2. The conditions of 2 remain. The fuel delivery is disabled.Turn the ECS to the START position.
Expected Result: The starting motor should cycle on and off according to setpoint P18 (cycle crank time).Results:
OK - If the starting motor cycles correctly, the problem is not present. STOP.
Not OK - If the starting motor remains ON and does not stop, the starting motor is faulty. Troubleshoot the starting motor. Refer to the Starting Motor and/or Engine Service Manuals. STOP.