22079940 Lower gear, complete Volvo.Penta
DPH-D; DPR-D; DPH-D1
Lower
Price: query
Rating:
Compatible models:
DPH-D; DPR-D; DPH-D1
Volvo.Penta
Volvo Penta entire parts catalog list:
Information:
Illustration 1 g00681895
System Schematic For Electronic Control Relay
Illustration 2 g00681904
System Schematic For Ignition Shutoff Relay (ISR)
Illustration 3 g00681915
System Schematic For Engine Control Switch (ECS)Note: It is critical that GSC+ setpoint P023 is correct for the engine application. Ensure that setpoint P023 is programmed correctly for the engine application before continuing with this procedure. There are several possible causes when a shutdown fault occurs and an engine does not shut down:
Operator Error: The operating conditions of the generator may not be understood by the operator. Ensure that the condition is one that should cause an engine shutdown.
Programming Error - Fault Is Overridden Or Disabled: It is possible to program the GSC+ in order to override certain shutdown faults. An overridden shutdown fault will be treated as an alarm fault. The YELLOW fault alarm indicator will be FLASHING instead of the RED fault shutdown indicator. If the GSC+ is programmed in order to disable a particular fault, there will not be any fault indicators or codes shown on the GSC+. In these cases, it is a good idea to check any setpoints related to that fault. For example, if a genset is not shutting down when an overvoltage fault occurs, make sure setpoint P104 (Overvoltage shutdown enable) is programmed correctly. It is also possible to program the engine ECM to override or ignore certain shutdown faults. See Troubleshooting, RENR5979, "G3500C Engines" or Troubleshooting, SENR2227, "G3408C and G3412C Engines" for more information on programming the engine ECM.
Programming Error - Setpoints Incorrect For Application Or Customer Needs: It is possible to program the GSC+ setpoints to a value that does not allow the situation to be recognized by the GSC+ as a shutdown condition. In this case, check the appropriate setpoints for correct values. For example, if the genset is not shutting down when a high coolant temperature condition occurs, make sure setpoint P015 (High Water Temperature Shutdown) is correct for the application.
Faulty Component: Some examples of faulty components that could prevent the GSC+ from shutting down the engine are: engine ECM, GSC+ and a broken or shorted harness wire.. In this case, the GSC+ or engine ECM will be issuing a command to shut down the engine due to a diagnostic code, but the engine remains running. Test Step 1. CHECK FOR DIAGNOSTIC CODES
Check the GSC+ for a diagnostic code on the upper display.Expected Result:The GSC+ should show a diagnostic code on the upper display.Results:
YES - The GSC+ shows a diagnostic code on the upper display.Repair: See theTesting and Adjusting section of this book for the diagnostic code that is displayed on the GSC+. Stop.
NO - The GSC+ does NOT show a diagnostic code on the upper display. Proceed to Test Step 2.Test Step 2. CHECK THE YELLOW FAULT ALARM INDICATOR
Check the display of the GSC+ for the yellow fault alarm indicator.Expected Result:The yellow fault alarm indicator is ON CONTINUOUSLY.Results:
YES - The yellow fault alarm indicator is ON CONTINUOUSLY. The GSC+ has been programmed to override the normal shutdown response. The setpoints have been modified and the GSC+ treats the condition as an alarm fault. The engine will continue to run.Repair: In order to view the setpoints, seeSystems Operation, "Engine/Generator Setpoint Viewing OP2-0". In order to reprogram the setpoints, see Systems Operation, "Engine/Generator Programming OP5-0". Stop.
NO - The yellow fault alarm indicator is not illuminated at all. Proceed to Test Step 3.Test Step 3. CHECK FOR THE RED FAULT SHUTDOWN INDICATOR
Check the display area of the GSC+ for the red fault shutdown indicator.Expected Result:The red fault shutdown should be FLASHING.Results:
YES - The red fault shutdown indicator is FLASHING and the engine remains running. Proceed to Test Step 4.
NO - All fault indicators are.OFF. A problem that is occurring should cause the GSC plus to shut down the engine. It is possible to program the GSC+ setpoints to a value that does not allow the situation to be recognized by the GSC+ as a shutdown condition.Repair: Check the appropriate setpoints for correct values. In order to view the setpoints, see System Operation, "Engine/Generator Setpoint Viewing OP2-0". In order to reprogram the setpoints, see System Operation, "Engine/Generator Programming OP5-0". Stop.Test Step 4. CHECK K1 INDICATOR ON GSC+ DISPLAY
The red fault shutdown indicator is FLASHING and the engine remains running.
Check the upper display of the GSC+.Expected Result:The K1 symbol is showing on the GSC+ upper display.Results:
YES - The K1 symbol is showing on the GSC+ upper display. The red fault shutdown indicator is FLASHING and the engine remains running. The GSC+ may have failed.Repair: The GSC+ may have failed. It is unlikely that the GSC+ has failed. Exit this procedure and perform this entire procedure again. If the problem remains, replace the GSC+. See Testing and Adjusting, "EMCP Electronic Control (Generator Set)-Replace" Stop.
NO - The K1 symbol is not showing at call on the GSC+ upper display. Proceed to Test Step 5.Test Step 5. CHECK THE GSC+ RELAY MODULE.The engine remains running and the red fault shutdown indicator is FLASHING.
In the generator housing, remove BOTH of the wires from RM-13 on the GSC+.Expected Result:The engine should shut down.Results:
OK - The engine shuts down. Repair: The GSC+ Relay Module may have failed. It is unlikely that the GSC+ Relay Module has failed. Exit this procedure and perform this entire procedure again. If the problem remains, replace the GSC+ Relay Module. See Testing And Adjusting, "EMCP Electronic Control (Relay Module) - Replace". Stop.
NOT OK - The engine runs and the engine will start. Proceed to Test Step 6.Test Step 6. CHECK THE SYSTEM BY USING THE ESPB.The engine remains running and the red fault shutdown indicator is FLASHING.
Push the emergency stop push button (ESPB).Expected Result:The engine should shut down.Results:
OK - The engine does shutdown. Proceed to Test Step 7
NOT OK - The engine does NOT shut down.Repair: The engine ECM made have failed. Refer to Troubleshooting, SENR1003, "3500B EPG Engines" or Troubleshooting, RENR2227, "3406E EPG Engines". Stop.Test Step 7. CHECK THE WIRING BETWEEN THE ENGINE ECM AND THE GSC+.The engine remains running and the red fault shutdown indicator
Parts lower Volvo Penta:
3801131
21550240
22079936
22079938
22079941
22079942
22079943
22079944